Fixing Single-Core Cable ・RVHS Series CCC/CE 450/750V Large Section Cable

Fixing Single-Core Cable ・RVHS Series CCC/CE  450/750V Large Section Cable

Move the mouse over the image to zoom

FEATURES  CCC/CE single core
●Certified by CCC and CE.
●PVC insulation allows for flexibility and heat resistance up to 70℃。
●Maximum cross section of 150mm2 is available.
●RoHS compliant.
a.Cut-to-length orders: enter requested length in the Length section (up to 100m)
b.Whole roll orders: enter 100 in the Length section.
NOTE:1 roll=100m
·MISUMI may make design changes without notice resulting in color and flexibility variations.
. Products with a section area of 80mm2 are not CCC-certified.

Part Number

Configured Part Number is shown.

Specification Table




ShapeSection Area
(mm2)
LengthCable
OD
(mm)
Reference
Weight
kg/km
Electrical PropertiesConductorInsulation
Maximum Allowable Curren A(30℃)Conductor Resistance
Ω/km
(20℃)
Insulation Characteristic
MΩ/km
(70℃)
Maximum Voltage
V/
minute
Core Wire Structure
pcs/mm
Outer Diameter
Approx.(mm)
ElectroplatingThickness
(mm)
Material
MAST-RVHS101~100
(Can be specified down to 1m increments)
6.6±0.3126851.91 or Less0.00562500322/0.1985±0.0154.6Not Provided1.0PVC
167.7±0.31881101.21 or Less0.0046518/0.1985±0.0155.71.0
259.7±0.33231450.78 or Less0.0044782/0.1985±0.0157.31.2
3510.7±0.353911800.554 or Less0.00381100/0.1985±0.0158.31.2
5012.88±0.355672300.386 or Less0.00371628/0.1985±0.01510.01.4
7014.8±0.357482850.272 or Less0.00322220/0.1985±0.01512.01.4
8015.6±0.48363100.238 or Less0.00322516/0.1985±0.01512.81.4
9516.9±0.410103450.206 or Less0.00323034/0.1985±0.01513.71.6
12018.4±0.4512554000.161 or Less0.00293848/0.1985±0.01515.21.6
15020.6±0.5515004700.129 or Less0.00294736/0.1985±0.01517.01.8

Overview/Features

Current Conductivity Coefficient in Case of Temperature Change
Environmental Temperature(℃)2030405060708090
Current Reduction Factor10.960.920.890.860.830.790.75
Allowable current value indicates the calculated value of 1 cable laid above ground in ambient temperature of 40℃, and is not a guaranteed value.
If the ambient temperature is 40℃ or above, the above current reduction factor is multiplied by the allowable current.


※ Note that the wire core number is “2” when the core number/pair number is marked as 1P.
※ The specification conversion is for reference only. For details, refer to the Line Number Table at >> Click here.
* Maximum allowable current is to be used only as a reference value and is not guaranteed.
※ Material Acronym
[Electroplating] Tin…Tinned Annealed Copper Wire
[Material] PVC…Polyvinyl chloride PE…Polyethylene materials
P…Polyester materials Fluorine…Various fluoro resins ※…Others
※The color and flexibility may vary with manufacturer.
Refer to the website for the latest information
Part Number
MAST-RVHS-50-[1-100/1]
MAST-RVHS-70-[1-100/1]
MAST-RVHS-80-[1-100/1]
MAST-RVHS-95-[1-100/1]
Part NumberStandard Unit PriceMinimum order quantityVolume DiscountDays to ShipConductor Cross Section
(mm2)
Representative Standard

-

1 Piece(s) 8 Day(s) 50CE / CCC

-

1 Piece(s) 7 Day(s) 70CE / CCC

-

1 Piece(s) 7 Day(s) 80CE

-

1 Piece(s) 7 Day(s) 95CE
Part Number
Part NumberStandard Unit PriceMinimum order quantityVolume DiscountDays to ShipConductor Cross Section
(mm2)
Representative Standard

Loading...

  1. 1

Basic Information

Rated Voltage 250V Shield None Properties Oil resistance / Chemical resistance
Sheath (outer coating) color Black Electroplating Tin Maximum Voltage 2000V /5 Minute