(!)Due to Microsoft's end of support for Internet Explorer 11 on 15/06/2022, this site does not support the recommended environment.

  • Notice of End of Sales for Economy Series Pneumatic Equipment Category. More information. 
  • Please note that E-Invoice will be sent to our customers by email. For more information, please read News. 

Block-Type Switching Power Supply S8TS (Part Numbers)

Block-Type Switching Power Supply S8TS

Omron product. Power supplies can be connected. Capacity increase is possible with dry cell batteries

[Features]
· 1 model can take 30-120W (12V type).
· 1 model can take 60-240W (24V type).
· Multi power supplies with different output voltages (5 V / 12V / 24V) are easy to configure.
· Uses N+1 redundant operation to help improve the reliability of power supply systems (12V/24V.)
· Lead-free soldering.
· Input condition: DC input DC80 to 370V (EC directives and various safety standards are not applicable).

PDF

Japanese Only

Part Number

Configured Part Number is shown.

S8TS-02505

Block-Type Power Supply (5/12/24 V Types) S8TS

Block-Type Power Supply S8TS: related images

S8TS appearance

Block-Type Power Supply S8TS: related images

Model S8TS-□□□□□ dimensional drawings

Block-Type Power Supply S8TS: related images

Model S8TS-□□□□□F dimensional drawings

Shared items / unit: mm
Guaranteed operating temperatures to -20°C (24 V type)

S8TS Types

Basic block, terminal block type

TypeInput VoltageOutput Voltage/CurrentModel
Basic Block Unit100 to 240 V AC5 V, 5 AModel S8TS-02505
12 V, 2.5 AModel S8TS-03012
24 V, 2.5 AModel S8TS-06024
Basic Block Unit
Bus Line Connector
One Each Of Model S8T-BUS01 And -BUS02 Included
24 V, 2.5 AModel S8TS-06024-E1

Basic block, connector terminal type

TypeInput VoltageOutput Voltage/CurrentModel
Basic Block Unit100 to 240 V AC24 V, 2.5 AModel S8TS-06024F

S8TS Ratings/Performance (Basic Block Unit)

24 V type, 12 V type (models S8TS-06024□/S8TS-03012□)

ItemSingle OperationParallel Operation
Efficiency (TYP.)24 V Type: 80% TYP.; 12 V Type: 73% TYP. (with rated input, 100% load)
Input ConditionsVoltage Range *1Rated: 100 to 240 V AC (Tolerance: 85 to 264 V AC; 80 to 370 V DC *8)
Frequency *150/60 Hz (47 to 63 Hz)
CurrentWith 100 V AC Input24 V Type: 1.0 A max.; 12 V Type: 0.7 A max.24 V Type: 1.0 A × (no. of blocks) max.; 12 V Type: 0.7 A × (no. of blocks) max.
At 200 V AC Input24 V Type: 0.5 A max.; 12 V Type: 0.4 A max.24 V Type: 0.5 A × (no. of blocks) max.; 12 V Type: 0.4 A × (no. of blocks) max.
Power Factor24 V Type: 0.9 min.; 12 V Type: 0.8 min. (with rated input, 100% load)
Harmonic Current RegulationConforms to EN61000-3-2
Leak CurrentWith 100 V AC Input0.35 mA max.0.35 mA × (no. of blocks) max.
With 240 V AC Input0.7 mA max.0.7 mA × (no. of blocks) max.
Inrush Current (25°C Cold Start) *5With 100 V AC Input17.5 A max.17.5 A × (no. of blocks) max.
At 200 V AC Input35 A max.35 A × (no. of blocks) max.
Output Characteristics *4Voltage Adjustment Range24 V Type: 22 to 28 V; 12 V Type: 12 V ±10% (with V.ADJ) *2
Ripple Noise Voltage2% (p-p) max.
Input Variation0.5% max. (with 85 to 264 V AC input, 100% load)
Load Variation2% max. (with rated input, 10 to 100% load)3% max. (with rated input, 10 to 100% load)
Startup Time1,000 ms max. (with 100/200 V AC rated input)
Output Hold Time *520 ms min. (with 100/200 V AC rated input)
Additional FunctionsOverload Protection *5105 to 140%; Inverted L Voltage Drop, Automatic Recovery100 to 140%; Inverted L Voltage Drop, Automatic Recovery
Overvoltage Protection *5 *6Yes
Parallel OperationYes (up to 4 blocks)
N+1 RedundancyYes (up to 5 blocks)
Series OperationYes
Undervoltage Indicator *5Yes (Color: Red)
Undervoltage Detection Output *5Yes (Open Collector Output), 30 V DC max., 50 mA max.
OtherAmbient Operating Temperature *5Refer to the derating curve (however, there should be no condensation or freezing)
Storage Temperature-25 to +65°C (however, there should be no condensation or freezing.)
Ambient Operating HumidityRelative Humidity of 25 to 85% (Storage relative humidity: 25 to 90%)
Dielectric Withstand Voltage3.0 kV AC for 1 min between (all inputs) and (all outputs) (Detection Current: 20 mA)
2.0 kV AC for 1 min between (all inputs) and (PE terminal) (Detection Current: 20 mA)
1.0 kV AC for 1 min between (all outputs) and (PE terminal) (Detection Current: 20 mA)
Insulation Resistance100 MΩ min. between (all outputs) and (all input/PE terminals) at 500 V DC
Vibration Resistance *7Must produce no abnormalities at 10 to 55 Hz, with single amplitude of 0.375 mm for 2 h each in 3 directions
Shock Resistance *7Must produce no abnormalities at 150 m/s2, 3 times each in 6 directions
Output Indicator LightYes (Color: Green)
Conducted Emissions *8Conforms with EN61204-3 Class B and complies with FCC Class A *9
Radiated Emissions *8Complies with EN61204-3 Class B *9
Safety Standards *824 V Type
UL Listed: UL508 (Listing, Class2 Output: Per UL1310) *3
UL UR: UL60950-1 (Recognition)
cUL Listed: CSA C22.2 No.107.1 (Class2 Output: Per CSA C22.2 No.223) *3
cUR: CSA C22.2 No.60950-1
EN/VDE: EN50178 (=VDE0160), EN60950-1 (=VDE0805 Teil1)
12 V Type
UL Listed: UL508 (Listing)
UL UR: UL60950-1 (Recognition)
cUL Listed: CSA C22.2 No.107.1
cUR: CSA C22.2 No.60950-1
EN/VDE: EN50178 (=VDE0160), EN60950-1 (=VDE0805 Teil1)
Weight450 g max.450 g × (no. of blocks) max.

*1. Do not use an inverter output for the power supply. Inverters with a specified output frequency of 50/60 Hz are available, but the rise in the internal temperature of the power supply may result in ignition or burning.
* 2. Please refer to the catalog for details on adjusting the output voltage for parallel operation.
   Setting to less than -10% may activate the undervoltage detection function.
   Ensure that the output capacity and output current after adjustment do not exceed the rated output capacity and rated output current respectively.
   Adjusting the V.ADJ may cause the output voltage to exceed the voltage adjustment range.
   When adjusting the output voltage, confirm the actual output voltage from the power supply and make sure there will be no damage to the load.
* 3. Please note that Class 2 approval does not apply for parallel operation.
* 4. Output characteristics are regulated at the power supply output terminals.
* 5. For details, please refer to the "Characteristics Data" listed below.
* 6. To reset, turn OFF the input power and let stand for at least 1 minute and then turn back on.
* 7. Make sure to mount end plates (model PFP-M) on both ends of the unit.
* 8. The range for compliance with EC Directives and safety standards (UL, EN, etc.) is 100 to 240 V AC (85 to 264 V AC).
* 9. The noise level depends on the wiring method and other factors. Insert one clamp filter (ZCAT2436-1330A by TDK) on the input line and ground line combined as a countermeasure for noise.

 

5 V type (model S8TS-02505□)

ItemSingle Operation
Efficiency (TYP.)73% TYP. (with rated input, 100% load)
Input ConditionsVoltage Range *1Rated: 100 to 240 V AC (Tolerance: 85 to 264 V AC; 80 to 370 V DC *7)
Frequency *150/60 Hz (47 to 63 Hz)
CurrentWith 100 V AC Input0.7 A max.
At 200 V AC Input0.4 A max.
Power Factor0.8 min. (with rated input, 100% load)
Harmonic Current RegulationConforms to EN61000-3-2
Leak CurrentWith 100 V AC Input0.35 mA max
With 240 V AC Input0.7mA max.
Inrush Current (25°C Cold Start) *5With 100 V AC Input17.5 A max.
At 200 V AC Input35 A max.
Output Characteristics *3Voltage Adjustment Range5 V ±10% (with V.ADJ) *2
Ripple Noise Voltage2% (p-p) max.
Input Variation0.5% max. (with 85 to 264 V AC input, 100% load)
Load Variation1.5% Max. (with rated input, 10 to 100% load)
Startup Time *41,000 ms max. (with 100/200 V AC rated input)
Output Hold Time *420 ms min. (with 100/200 V AC rated input)
Additional FunctionsOverload Protection *4105 to 140%; Inverted L Voltage Drop, Automatic Recovery
Overvoltage Protection *4 *5Yes
Parallel OperationNot applicable
N+1 RedundancyNot applicable
Series OperationYes (External Diode Required)
Undervoltage Indicator *4Yes (Color: Red)
Undervoltage Detection Output *4Yes (open collector output), 30 V DC max., 50 mA max.
OtherAmbient Operating Temperature *4Refer to the derating curve (however, there should be no condensation or freezing)
Storage Temperature-25 to +65°C (however, there should be no condensation or freezing.)
Ambient Operating HumidityRelative humidity of 25 to 85% (Storage relative humidity: 25 to 90%)
Dielectric Withstand Voltage3.0 kV AC for 1 min between (all inputs) and (all outputs) (Detection Current: 20 mA)
2.0 kV AC for 1 min between (all inputs) and (PE terminal) (Detection Current: 20 mA)
1.0 kV AC for 1 min between (all outputs) and (PE terminal) (Detection Current: 20 mA)
Insulation Resistance100 MΩ min. between (all outputs) and (input/PE terminals) at 500 V DC
Vibration Resistance *6Must produce no abnormalities at 10 to 55 Hz, with single amplitude of 0.375 mm for 2 h each in 3 directions
Shock Resistance *6Must produce no abnormalities at 150 m/s2, 3 times each in 6 directions
Output Indicator LightYes (Color: Green)
Conducted Emissions *7Conforms with EN61204-3 Class B and complies with FCC Class A
Radiated Emissions *7Complies with EN61204-3 Class B
Safety Standards *7UL Listed: UL508 (Listing)
UL UR: UL60950-1 (Recognition)
cUL Listed: CSA C22.2 No.107.1
cUR: CSA C22.2 No.60950-1
EN/VDE: EN50178 (=VDE0160), EN60950-1 (=VDE0805 Teil1)
Weight450 g max.

*1. Do not use an inverter output for the power supply. Inverters with a specified output frequency of 50/60 Hz are available, but the rise in the internal temperature of the power supply may result in ignition or burning.
*2. Setting to less than -10% may activate the undervoltage detection function.
   Ensure that the output capacity and output current after adjustment do not exceed the rated output capacity and rated output current respectively.
   Adjusting the V.ADJ volume may increase the voltage by +10% or more of the voltage adjustment range.
   When adjusting the output voltage, confirm the actual output voltage from the power supply and make sure there will be no damage to the load.
*3. Output characteristics are regulated at the power supply output terminals.
*4. For details, please refer to the "Characteristics Data" listed below.
*5. To reset, turn OFF the input power and let stand for at least 1 minute and then turn back on.
*6. Make sure to mount end plates (model PFP-M) on both ends of the unit.
*7. The range for compliance with EC Directives and safety standards (UL, EN, etc.) is 100 to 240 V AC (85 to 264 V AC).

S8TS Characteristics Data (Derating Curves)

Parallel operation and side-by-side mounting

Block-Type Power Supply S8TS: related images

Imaging showing parallel operation and side-by-side mounting

Block-Type Power Supply S8TS: related images

5 V/12 V type graph

Block-Type Power Supply S8TS: related images

24 V type

Single operation with spaced installation

Block-Type Power Supply S8TS: related images

Image showing single operation with spaced installation

Block-Type Power Supply S8TS: related images

5 V/12 V graph

Block-Type Power Supply S8TS: related images

24 V graph

  • *Please refer to the catalog for any product information not listed above.
Part Number
S8TS-02505
Part NumberStandard Unit PriceMinimum order quantityVolume DiscountDays to ShipCapacity
(W)
Output voltage (Single only) Rated output current (single only)
(A)
Included Function

MYR 636.55

1 Piece(s) 5 Day(s) or more 25DC5V5Alarm Output

Loading...

  1. 1
 

Basic Information

Shape DIN rail direct attachment Single/multi Single Input Voltage AC/DC
Input/output terminal shape Screw Safety standards CE / UL / CUL Dimension height(mm) 128.1
Dimension width(mm) 48 Dimension depth(mm) 120

Please check the type/dimensions/specifications of the part S8TS-02505 in the Block-Type Switching Power Supply S8TS series.

Products like this...

Part Number
S8TS-03012
S8TS-06024
Part NumberStandard Unit PriceMinimum order quantityVolume DiscountDays to ShipCapacity
(W)
Output voltage (Single only) Rated output current (single only)
(A)
Included Function

MYR 641.16

1 Piece(s) 5 Day(s) or more 30DC12V2.5Parallel / Alarm Output

MYR 641.16

1 Piece(s) 2 Day(s) 60DC24V2.5Parallel / Alarm Output

Additional Products in this Category

Customers Who Viewed This Item Also Viewed

Tech Support

Factory Automation, Electronics, Tools, & MRO (Maintenance, Repair and Operations)
Tel:(60) 3 7890 6399
9:00am - 6:00pm (Monday - Friday)
9:00am - 1:00pm (Saturday)