(!)Due to Microsoft's end of support for Internet Explorer 11 on 15/06/2022, this site does not support the recommended environment.
A wide variety of standard and configurable components for factory automation engineers in industries such as automotive, semiconductor, packaging, medical and many more.
A good selection of accessories such as screws, bolts, washers and nuts that you may need for your daily engineering usage.
Browse industrial materials ranging from heat insulating plates, sponges, to metal and plastic materials in different sizes to meet your various applications.
A wide variety of wiring parts for connecting and protecting control and PC parts including Connectors, Cables, Electric Wires, Crimping Terminals and more.
A wide variety of controls and PC parts for electrical engineers including Controls, Powers, PC parts and more.
A wide variety of cutting tools for many uses and work materials including End Mills, Drills, Cutters, Reamers, Turning Tools and more.
A wide variety of tools and supplies used in processing including Machine Tools, Measurement Tools, Grinding and Polishing Supplies and more.
A wide variety of goods used in shipment, material handling and warehouse including Tape supplies, Stretch film, Truck, Shelf, Crane and more.
A large variety of goods for every kind of factories and offices including Protection items, Cleaning supplies, sanitations, office supplies and more.
A large variety of items used in R&D and Clean Room including research Equipment, Laboratory Essentials, Analysis Supplies, Clean Environment-Related Equipment and more.
Choose from thousands of standard stamping die components including Punch & Die, Gas Springs, Guide Components, Coil Springs and many more.
Browse our wide variety of mold components including Ejector Pins, Sleeves, Leader Components, Sprue Bushings and many more.
Browse our injection molding components including Heating Items, Couplers, Hoses and more.
[Features]
· A series based on twin timer, star delta timer.
· UL, CSA, LR, NK, CCC acquired, EN61812-1 compatible safe design.
· Compatible with the CE mark.
· Because the time units enable separate ON time and OFF time setting, combinations of long term ON or OFF and short time ON or OFF are possible.
· Product line-up with the two types of operational mode of start flicker ON and start flicker OFF.
· Power sources for any low voltage (AC24 to 48/DC12 to 48V), any high voltage (AC100 to 240V/DC100 to 125V).
· 24 types of time ranges can be selected from among 0.05 seconds to 300 hours.
· Instantaneous output of 0 setting is possible.
· Because there is instantaneous output by revolving the scale in the direction of 0, the checking of the sequence operation and the like is simple.
· UL, CSA, NK, LR, CCR acquired, EN61812-1 compatible.
· Corresponds to the CE mark.
Japanese Only
Part Number
Configured Part Number is shown.
H3CR-G8L AC100-120
H3CR-F /-G / -H external appearance
Because the time units enable separate ON time and OFF time setting, combinations of long term ON or OFF and short time ON or OFF are possible.
Product range includes 2 types of operational modes: start flicker ON and start flicker OFF.
Power supplies for low voltage (24 to 48 V AC / 12 to 48 V DC) and high voltage (100 to 240 V AC / 100 to 125 V AC) can be freely selected.
24 types of time ranges can be selected, from 0.05 seconds to 300 hours.
Instantaneous output for zero set value is possible. There is instantaneous output by turning the scale in the 0 direction, making it easy to confirm sequence operations, etc.
Complies with UL, CSA, NK, LR, and CCC, and is EN61812-1 compliant. Conforms to the CE mark.
4 types of time ranges can be selected with a single device, from 0.5 seconds to 120 seconds.
Complies with UL, CSA, NK, and LR, and is EN61812-1 compliant. Conforms to CE mark, CCC*
*Series H3CR-G8L-30/-G8EL-31 are not compliant with safety standards.
4 types of time ranges can be selected for each series, from 0.05 seconds to 12 seconds for the S series and from 0.05 minutes to 12 minutes for the M series.
Complies with UL, CSA, NK, and LR, and is EN61812-1 compliant. Conforms to CE mark, CCC.
Variations In Operating Time | ±0.2% (percentage relative to maximum scale) or less (±0.2%, ±10 ms or less in the 1.2‑s, 3‑s range) | |
---|---|---|
Set Error | ±5% (percentage relative to maximum scale) ±50 ms or less | |
Recovery Time | 0.1 s Or Less | |
Voltage Effect | ±0.2% (percentage relative to maximum scale) or less (±0.2%, ±10 ms or less in the 1.2‑s, 3‑s range) | |
Temperature Effect | ±1% (percentage relative to maximum scale) or less (±1%, ±10 ms or less in the 1.2‑s, 3‑s range) | |
Insulation Resistance | 100 MΩ or more (at 500 V DC megger) | |
Withstand Voltage | 2,000 V AC, 50/60 Hz, 1 min (between charging metal part and non-charging metal part) 2,000 V AC, 50/60 Hz, 1 min (between control output and operation circuit) 2,000 V AC, 50/60 Hz, 1 min (between different pole contacts) 1,000 V AC, 50/60 Hz, 1 min (between discontinuous contacts) | |
Impulse Voltage | 5 kV (between power supply terminals); however, 1 kV for 24 to 48 V AC / 12 to 48 V DC types 5 kV (between conductive part terminal and exposed non-charging metal part) However, 1.5 kV for 24 to 48 V AC / 12 to 48 V DC types | |
Noise Resistance | Square-wave noise by noise simulator (pulse width 100 ns/1 μs rise 1 ns) ±1.5 kV (between power supply terminals) | |
Electrostatic Strength | 8 kV (Malfunction) 15 kV (Destruction) | |
Vibration | Endurance | 10 to 55 Hz, half amplitude 0.75 mm, 3 directions, 2 h each |
Malfunction | 10 to 55 Hz, half amplitude 0.5 mm, 3 directions, 10 min each | |
Shock | Endurance | 980 m/s2, 6 directions, 3 times each |
Malfunction | 98 m/s2, 6 directions, 3 times each | |
Life | Mechanical | 20 million operations or more (no load, switching frequency 1,800 operations/h) |
Electrical | 100,000 operations or more (250 V AC, 5 A, resistive load, switching frequency 1,800 operations/h)* | |
Protection Structure | IP40 (Panel Surface) | |
Mass | Approx. 100 g |
Series H3CR-F, H3CR-FN external shape
Series H3CR-F, H3CR-FN dimensional drawing
Part Number |
---|
H3CR-G8L AC100-120 |
Part Number | Standard Unit Price | Minimum order quantity | Volume Discount | Days to Ship | Time specifications (s) | Power Supply Voltage | Dimension depth (mm) | Rated power supply voltage (V) |
---|---|---|---|---|---|---|---|---|
MYR 310.73 | 1 Piece(s) | 5 Day(s) or more | 0.4~120s | AC-dedicated | 63.7 | AC100 to 120 |
Loading...
Type | Timer | Display method | Analog | Mounting Method | Panel / surface mount (shared) |
---|---|---|---|---|---|
Output Method | Relay | Dimension vertical(mm) | 48 | Dimension width(mm) | 48 |
Time ranges = N | 24 range | Contact Configuration | 2c |
Please check the type/dimensions/specifications of the part H3CR-G8L AC100-120 in the Solid-state Timer H3CR-F / -G / -H series.
Part Number |
---|
H3CR-F8 AC24-48/DC12-48 |
H3CR-F8N AC100-240/DC100-125 |
H3CR-F8N AC24-48/DC12-48 |
H3CR-G8L AC200-240 |
H3CR-G8L-30 AC100-120 |
H3CR-G8L-30 AC200-240 |
Part Number | Standard Unit Price | Minimum order quantity | Volume Discount | Days to Ship | Time specifications (s) | Power Supply Voltage | Dimension depth (mm) | Rated power supply voltage (V) |
---|---|---|---|---|---|---|---|---|
MYR 411.43 | 1 Piece(s) | 2 Day(s) | 0.05s to 300h | AC/DC | 52.3 | AC24 to 48/DC12 to 48 | ||
MYR 412.65 | 1 Piece(s) | 5 Day(s) or more | 0.05s to 300h | AC/DC | 52.3 | AC100 to 240/DC100 to 125 | ||
MYR 411.43 | 1 Piece(s) | 2 Day(s) | 0.05s to 300h | AC/DC | 52.3 | AC24 to 48/DC12 to 48 | ||
MYR 310.82 | 1 Piece(s) | 2 Day(s) | 0.4~120s | AC-dedicated | 63.7 | AC200 to 240 | ||
MYR 309.04 | 1 Piece(s) | 5 Day(s) or more | 0.4~120s | AC-dedicated | 63.7 | AC100 to 120 | ||
MYR 310.58 | 1 Piece(s) | 5 Day(s) or more | 0.4~120s | AC-dedicated | 63.7 | AC200 to 240 |
How can we improve?
How can we improve?
While we are not able to respond directly to comments submitted in this form, the information will be reviewed for future improvement.
Customer Privacy Policy
Thank you for your cooperation.
While we are not able to respond directly to comments submitted in this form, the information will be reviewed for future improvement.
Please use the inquiry form.
Customer Privacy Policy