CJ1W-AD04U

Process I/O Unit Specifications

CJ Series Process I/O Unit: related images

CJ1W-AD04U outline drawing

Specifications

  • Signal range: full multi input: Pt 100, JPt 100, Pt 1000, K, J, T, L, R, S, B, 4 to 20 mA, 0 to 20 mA, 1 to 5 V, 0 to 5 V, 0 to 10 V
  • Conversion speed: 250 ms / 4 points
  • Accuracy (at ambient temperature of 25°C)
    Accuracy: platinum resistance thermometer input: (the larger of ±0.3 of PV or ±0.8°C ) ±1 digit or less
    Thermocouple input: (Larger of ±0.3% of PV) ±1 digit or less *1
    Voltage/current input: (±0.3% of F.S.) ±1 digit or less
  • Current consumption: 0.32 A (5V Series)

*1. L and −100°C or less for K and T are ±2°C ±1 digit max. 200°C or less for R and S is ±3°C±1 digit max. B less than 400°C is not covered by the warranty.

Specifications

ItemSpecifications
Unit GroupCJ Series High Function I/O Unit
External Dimensions (mm)31 (W) × 90 (H) × 65 (D)
Weight150 g or less
External Connection Terminals18-Point removable terminal block (M3 screws, correct tightening torque of 0.5 N·m)
Unit No. of Setting Switches00 to 95
Self-Diagnostic FunctionDiagnostic results displayed via the LEDs
Mountable PositionCPU equipment or CJ series expansion devices
Number of Installable Units40 (Installation of 10 units × 4 racks)
The total current consumption for all units (including CPU unit, etc.) equipped for each (CPU unit or expansion device) must be less than the maximum supplied power for the power supply unit
Ambient Operating Temperature0 to 55°C
Ambient Operating Humidity10 to 90% RH (assuming no condensation)
ItemSpecifications
FormatModel CJ1W-AD04U
Applicable ControllersCJ/NJ Series
Unit TypesCJ Series high-functioning I/O unit
Mountable PositionCPU unit, expansion device
Number of Installable Units40 units (must be within current consumption and power consumption range)
Number Of Configurable Units00 to 95 (No duplicating for high-functioning I/O units)
Data Exchange Area With CPU UnitHigh-Functioning I/O Unit
CIO Area
(Operation Data)
10 CH/Unit
This unit → CPU unit: all process values, process value alarms (L, H), conversion data enabled flags, input error, cold junction sensor errors
High-Functioning I/O Unit
Allocated DM Area
(Setting Parameters)
100 words/unit
CPU unit → this unit: input types, scaling maximum/minimum values, process value alarm settings values (L, H), zero span adjustment value, warning on delay time, warning hysteresis, memory area settings allocated for expansion
Memory Area Allocated for Expansion
(Expansion Settings Parameters)
1 CH/unit
CPU unit → this unit: process value alarm output
Inputs4
Input TypePlatinum Resistance Thermometer: Pt100 (JIS, IEC), Pt1000, JPt100
Thermocouple: K, J, T, L, R, S, B
Current: 4 to 20 mA, 0 to 20 mA
Voltage: 1 to 5 V, 0 to 5 V, 0 to 10 V
The input type can be set individually for each input
Scaling (Voltage/Current Input)Voltage and current input data to be stored in the allocated words in the CIO area must be scaled (with the minimum and maximum values set by user) (4 points set separately)
Data Storage in the CIO AreaVoltage/Current Input:
The value derived from carrying out the following processing in order of the actual process data in the input range is stored in four digits hexadecimal (binary values) in the allocated words in the CIO Area.
1) Scaling →2) Zero/span adjustment → 3) Output limits
Temperature input:
The value derived from carrying out the following processing in order of the actual process data in the input range is stored in four digits hexadecimal (binary values) in the allocated words in the CIO Area.
1) ⁰C, °F conversion → 2) Zero/span adjustment → 3) Output limits
(temperatures are typically stored at 10 times the value)
Accuracy (25°C) (Sensor Error not Included)Platinum Resistance Thermometer input: (Larger of specified value ±0.3% or ±0.8°C) ±1 digit max.
Thermocouple input: (Larger of specified value ±0.3% or ±1.5°C) ±1 digit or less
However
L: ±2°C ±1 digit max.
−100°C or less for K and T: ±2°C ±1 digit max.
200°C or less for R and S: ±3°C ±1 digit max.
400°C for B or less not specified
Voltage/current input: (±0.3% F.S.) ±1 digit max.
Temperature Coefficient±100 ppm F.S./°C max.
Resolution1/12,000 (with voltage/current input)
See catalog section "Input Types and Input Ranges" for temperature inputs
Input Signal RangeVoltage/current input: -5% to 105% of the input range set in scaling
Temperature input: ±20°C or ±20°F relative to upper and lower limits for each sensor range
Maximum Rated InputVoltage input: ±15 V, Current input: 30 mA
Input ImpedanceTemperature input: 10 kΩ min., Voltage input: 1 MΩ min., Current input: 250 Ω (fixed)
Warmup Time30 mins.
Thermocouple InputUses internal sensors for cold junction compensation
Platinum Resistance Thermometer Input· Measurement method: 3 wire method
· Allowable conductor resistance: 20 Ω max. per wire
· Input detection current: 1.1 mA
Conversion Period250 ms/4 inputs
Maximum Time to Store Data in CPU UnitConversion period + one CPU unit cycle
Disconnection DetectionDisconnections can be detected at each input (excluding voltage/current input of 0 to 20 mA, 0 to 5 V, and 0 to 10 V)
Detection level
· Temperature input: When exceeding 20°C or 20°F relative to the upper and lower limits for each sensor range
· +1 to +5 V: input signal < 0.3 V
· 4 to 20 mA: input signal < 1.2 mA
For connection interruptions or when out of input range, the disconnection detection flag is switched ON
The process value overrange direction for when a disconnection occurs can be specified
Process Value AlarmThe process value 2-point alarm (L, H), hysteresis and on delay timer (0 to 60 s) can be set
The process value alarm bit can be copied to a address in the available memory area allocated for memory
InsulationBetween input and controller signal: power supply = transformer, signal = photo coupler
Between all inputs: power supply = transformer, signal = photo coupler
Insulation ResistanceBetween mutual batch channels: 20 MΩ (with 500 V DC ohmmeter)
Dielectric StrengthBetween mutual batch channels: 500 V AC, 50/60 Hz for 1 minute, Leakage current 1 mA max.
External ConnectionTerminal block (removable)
DisplayFront: LED × 3 (for normal operation, errors detected by unit, errors detected by CPU unit)
Setting PartFront rotary switch: Unit number (0 to 95)
Current Consumption (Supplied by Power Supply Unit)5 V DC, 320 mA max.
External Dimensions (mm)31 (W) × 90 (H) × 65 (D)
Weight150 g or less

*1. Square root calculation function is possible only during DC input. The square root is not extracted for temperature input. The square root calculation function is only available when the maximum scaling value is greater than the minimum scaling value. The square root is not extracted when the maximum scaling value is less than the minimum scaling value. When the square root function is used, set the scaling values after square root calculation (e.g., for flow rates or other values) for the process value scaling A and B settings.
*2. The cold junction compensation method specification function is available only for thermocouple inputs.
*3. The resistance thermometer input compensation function is only available for the resistance thermometer input.

CJ Series Process I/O Unit: related images

Outline drawing

CJ Series Process I/O Unit: related images

System configuration

Part Number
CJ1W-AD04U
Part NumberStandard Unit PriceMinimum order quantityVolume DiscountDays to Ship

MYR 2,550.18

1 Piece(s) 5 Day(s) or more

Loading...

  1. 1
 

Basic Information

Type Input Input Type Voltage / Current / Thermocouple / Temperature Measuring Resistor Number of Input Channels 4
Input Range Other A/D Conversion Speed (Conversion Time) Less than 100 to 500 ms Terminal shape Terminal Block
Representative Standard CE / UL / CUL / CSA Consumed current (5 V system)(A) 0.32 Input Signal Range Pt 100, JPt 100, Pt 1000, K, J, T, L, R, S, B, 4 to 20 mA, 0 to 20 mA, 1 to 5 V, 0 to 5 V, 0 to 10 V

Please check the type/dimensions/specifications of the part CJ1W-AD04U in the CJ series process input/output unit series.

Additional Products in this Category

Customers Who Viewed This Item Also Viewed

Tech Support

Factory Automation, Electronics, Tools, & MRO (Maintenance, Repair and Operations)
Tel:(60) 3 7890 6399
9:00am - 6:00pm (Monday - Friday)
9:00am - 1:00pm (Saturday)