  • Kindly be informed that it will be peak period in conjunction with the Chinese New Year festive season. Delivery pickup upon 25 January 2025 estimated would arrive after CNY holidays. Please expect slight delay for orders shipped during this peak season and we thank you for your kind understanding. [Details]
  • Please note that E-Invoice will be sent to our customers by email. For more information, please read News. 

Solid State/Timer H3DK-H

Solid State/Timer H3DK-H

DIN22.5 mm-width standard timer series power OFF-delay timer

[Features]
· For DIN22.5 mm width control panels.
· Standard timer series.
· AC/DC free power source compatible (AC/DC24 to 240V).
· DC12V powered type has been added every series.
· UL, CSA, NK, LR, CCR acquired, EN61812-1 compatible.
· Compatible with the CE mark.
· Conforms with the EMC standard EN61812-1, so can be used in an industrial environment but also in residential, sales and light industry.
· A terminal construction with secure screw fittings that prevents against hazardous contact (EN50274 compliant).

PDF

Japanese Only

Solid-State Timer Specifications

Solid-State Timer H3DK-H: related image

H3DK-H external appearance

Solid-State Timer H3DK-H: related image

H3DK-H dimensional outline drawing, units: mm

Solid-State Timer H3DK-H: related image

H3DK-H dimensional outline drawing, units: mm

Power Supply Voltage· 100 to 120 V AC, 50/60 Hz
· 200 to 240 V AC, 50/60 Hz
· 24 to 48 V AC / V DC, 50/60 Hz *1
Allowable Voltage Variation Range85 to 110% of rated voltage
Power
Consumption
Series H3DK-HCS/-HCLAt 120 V AC: 11.7 VA or Less
Series H3DK-HDS/-HDLAt 240 V AC: 29.5 VA or Less
Series H3DK-HBS/-HBLAt 48 V AC: 1.2 VA or Less *2
Control OutputContact output: 250 V AC 5 A resistive load (cosφ = 1), 30 V DC 5 A resistive load *3
Contact material: Ag alloy
Operating Temperature Range-20 to +55°C (No Freezing)
Storage Temperature Range-40 to +70℃ (No Freezing)
Ambient Operating Humidity25 to 85%
  1. *1 DC power supply ripple is 20% or less (usable up to single-phase full-wave rectification power supply).
  2. *2 For the DC reference power consumption, see "● DC Power Consumptions (Reference Information" in the catalog.
  3. *3 The control output rating is for a discrete H3DK unit. When 2 or more are used side by side, see "Installation Pitch and Output Switching Capacity (Reference Values)" in the catalog.

*Refer to the catalog for specifications other than those listed above.

Part Number
H3DK-HBL AC/DC24-48
H3DK-HBS AC/DC24-48
H3DK-HDS AC200-240V
Part NumberStandard Unit PriceMinimum order quantityVolume DiscountDays to ShipTime specifications
(s)
Power Supply Voltage Rated power supply voltage
(V)

MYR 410.82

1 Piece(s) 5 Day(s) or more 1s to 120sAC/DCAC/DC24 to 48

MYR 410.82

1 Piece(s) 2 Day(s) 0.1s to 12sAC/DCAC/DC24 to 48

MYR 410.82

1 Piece(s) 2 Day(s) 0.1s to 12sAC-dedicatedAC200 to 240V

Loading...

  1. 1
 

Basic Information

Display method No display function Mounting Method DIN rail mount Output Method Relay
Dimension vertical(mm) 89.4 Dimension width(mm) 22.5 Dimension depth(mm) 100
Time ranges = N 2 range Contact Configuration 1c

Additional Products in this Category